Voltage, Current and Power in Three-Phase Systems

Derive the relations between line and phase quantities in a balanced three-phase circuit and compute numerical results. Active, reactive and apparent power.

Save your circuit

Learning Outcomes

Topic Explanation

Physical basis of three-phase generation

A three-phase system generates three sinusoidal voltages that are shifted by 120 electrical degrees relative to each other. This arrangement offers two main advantages over single-phase generation: more power is transmitted with the same conductive material, and the instantaneous power sum of the three phases remains constant over time. Constant power flow reduces torque ripple in generator and motor shafts, which is why large electrical machines and transmission lines are installed in three phases. The equal angle between the phases also ensures that the sum of the three vectors is zero at all times.

Phase sequence is the order in which the voltages reach their peaks and is designated as A-B-C. Swapping two phases creates a reverse phase sequence; since this reverses the direction of the rotating field, the asynchronous motor operates in the opposite direction. For this reason, verifying the phase sequence of a generating unit to be connected to the grid is one of the basic checks performed before connection. A phase sequence error changes not only the direction of rotation of the motor, but also the component signs measured by the protection schemes.

Wye and delta connection relationships

In a star connection, the phase voltage is equal to the line voltage divided by the square root of three, and the line current is equal to the phase current. The neutral conductor carries the vectorial sum of the phase currents when the load is unbalanced; with a balanced load, this sum is zero. Therefore, a neutral conductor is present in low-voltage distribution, and measuring devices are based on the phase-to-neutral voltage. The center of the star connection also provides a natural reference point for grounding and residual current protection.

In a delta connection, the line voltage is equal to the phase voltage, and the line current is the square root of three times the phase current. The closed loop of the delta connection helps the magnetic flux in the transformer winding to remain sinusoidal, as it allows third harmonic currents to circulate. Since there is no neutral output, it is not appropriate to directly connect single-phase loads. Delta connection is commonly preferred in medium-voltage motors and in one winding of transmission transformers.

Active, reactive and apparent power

Apparent power S is the product of the effective values of voltage and current and is expressed in volt-amperes. Active power P is the product of apparent power multiplied by the cosine of the phase angle between voltage and current; this is the part that does real work and generates heat. Reactive power Q is the sine term and represents the energy that oscillates back and forth to establish a magnetic field. The relationship between the three quantities is represented by the right triangle relation, where the square of S is equal to the sum of the square of P and the square of Q.

Inductive loads shift the current backward from the voltage and consume reactive power in the positive direction, while capacitive loads shift the current forward. If reactive power is not generated on-site in grid operation, it has to be transmitted from a remote source, and this transmission creates additional current in the lines, and therefore additional losses. Therefore, the reactive power balance is directly related to maintaining the voltage level. The power factor of a consumer is the ratio of active power to apparent power and varies between zero and one.

Effect of power factor on losses

For a constant active power, the current increases as the power factor decreases, because the current is calculated by dividing the active power by the square root of three times the voltage times the power factor. Since line loss varies with the square of the current, when the power factor is increased from 0.7 to 0.95, the current required for the same power decreases by approximately twenty-seven percent, and the loss is almost halved. This simple calculation shows that reactive compensation is not only a measurement parameter, but also a measure that increases transmission capacity.

Capacitor banks reduce the line current by providing the reactive power required by inductive loads at the point of use. However, overcompensation creates a capacitive power factor and can increase voltage, which is particularly problematic on lightly loaded lines. Gradual or continuously adjustable compensation is necessary to adapt to changes in load. If harmonics are present, capacitors pose a risk of resonance; Therefore, the system impedance is considered together when making a selection.

Unbalanced load and neutral current

When the three-phase loads are not equal, the amplitudes and phase angles of the phase currents differ. The neutral conductor carries the vectorial difference of these three currents and, in some cases, can even be greater than the phase currents. Third harmonic currents accumulate in the neutral conductor, especially in buildings where single-phase electronic loads are concentrated. Selecting a weak neutral conductor causes overheating and voltage imbalance.

Imbalance creates negative and zero sequences in addition to the positive sequence. The negative component creates a field that rotates in the opposite direction in asynchronous motors and causes additional heating and a reduction in torque. The zero component, on the other hand, is seen in the neutral and ground path; it can cause protection systems to malfunction. Rearranging the load distribution between phases is the simplest and most effective way to reduce imbalance.

RMS value and phasor representation

Since alternating current quantities change instantaneously, the root-mean-square (RMS) value is used in heat and power calculations. The effective value is equal to the direct current value that generates the same amount of heat in the same resistance; it is the peak value of a sinusoidal quantity divided by the square root of two. Most measuring instruments display the RMS value; however, in waveforms containing harmonics, there is a difference between the true RMS value and the fundamental frequency component.

Phasor representation expresses the sinusoidal quantity as a single complex number with an amplitude and a phase angle. With this representation, differential equations become algebraic equations, and circuit analysis can be performed using Kirchhoff's laws. In the power calculation, the voltage phasor is multiplied by the conjugate of the current phasor; the real part of the resulting complex number gives the active power, and the imaginary part gives the reactive power. The phasor is only meaningful for quantities at the same frequency.

Voltage levels and transmission architecture

Energy is usually generated at low voltage at the point of production; when it is transmitted over long distances, the voltage is increased and the current is reduced. If the voltage is increased tenfold for the same power, the current decreases to one-tenth and the transmission loss decreases to one percent. Therefore, long-distance transmission is carried out at high voltage; as the voltage increases, the cost of insulation and the corona effect become more important.

The grid consists of the generation, transmission, sub-transmission, and low-voltage distribution layers. At each layer, transformers step down the voltage and create protection and measurement points. The voltage level is selected by evaluating the power to be transmitted, the distance, the environmental conditions, and the compatibility of the existing equipment together. The neutral and grounding arrangement at low voltage is decisive for user safety.

Per-unit system

The per-unit method divides each quantity by a selected base value and enables working with dimensionless numbers. The voltage, current, power, and impedance bases are interrelated; the impedance base is found by dividing the square of the voltage base by the power base. With this method, elements at different voltage levels can be compared in the same diagram, and the transformer ratio is not calculated separately.

The base power is selected as common for the entire grid, while the base voltage is taken as the nominal value of each voltage level. The results are generally in the range of 0.9 to 1.1; these numbers directly indicate the voltage deviation. Per-unit values increase numerical stability in short-circuit and power flow calculations and prevent unit conversion errors.

Line model and voltage drop

Short lines are modeled with impedance consisting of series resistance and reactance; shunt capacitance is also added for medium and long lines. The voltage drop is calculated approximately as the sum of current multiplied by resistance multiplied by the power factor and current multiplied by reactance multiplied by the sine term. Since the ratio of resistance to reactance is high in distribution lines, the active power flow significantly affects the voltage. In transmission lines, the reactive component is dominant, and voltage is mostly related to reactive power.

The pi model of the line divides the total shunt capacitance into two halves and places them at the ends. This model accurately reflects the voltage profile and charging current on long lines. On high-voltage open lines, the capacitive charging current can raise the voltage above the nominal value; this indicates that compensation devices should be switched off under light load conditions.

Transmission capacity and limits

The power that a line can carry is determined by three main limits: the thermal limit of the conductor, the voltage drop limit, and the stability limit. The thermal limit is decisive for short lines, while the stability limit is decisive for long lines. The thermal limit depends on the ambient temperature, wind, and the condition of the conductor; therefore, the same line carries different capacities in different seasons.

The voltage limit is defined by the lowest permissible voltage at the receiving end, and it is generally not allowed to fall more than a few percent below the nominal value. The stability limit is related to the loss of synchronization when the power transmitted along the line exceeds a certain value. The operator takes the lowest of these three limits as a basis; dynamic line rating recalculates the thermal limit with real-time measurement.

Key Points

Worked Examples

Worked Example

Worked Example

Worked Example

Worked Example

Worked Example

Worked Example

Common Mistakes

Tips

Practice Questions

  1. 1. In a three-phase system, what is the electrical angle between the phases in degrees?
  2. 2. In a balanced star connection, how many times the phase voltage is the line voltage?
  3. 3. In a balanced delta connection, how many times the phase current is the line current?
  4. 4. What is the unit of active power?
  5. 5. What is the relationship between apparent power and active power?
  6. 6. How is the current positioned relative to the voltage in an inductive load?
  7. 7. What is the reactive power sign of a capacitive load?
  8. 8. How is the power factor defined?
  9. 9. How does the line current change if the power factor decreases at constant active power?
  10. 10. What is the source of the square root of three factor in the three-phase power relationship?
  11. 11. What is the neutral current in a balanced three-phase system?
  12. 12. What is the result of a reverse phase sequence?
  13. 13. Where do third harmonic currents mostly accumulate?
  14. 14. What quantity is the effective value equal to?
  15. 15. In a sinusoidal voltage, how many times the peak value is the rms value?
  16. 16. Under what conditions is phasor representation meaningful?
  17. VOLUME 17 How is the current phasor used in complex power calculation?
  18. 18. How is the per-unit impedance base found?
  19. 19. What is the main benefit of the per-unit system?
  20. 20. Which element is not included in the short-line model?
  21. 21. Which component does voltage drop in distribution lines depend on the most?
  22. 22. With which power is voltage most often associated in transmission lines?
  23. 23. What causes the voltage to rise on a long open line?
  24. 24. Which group of limits determines the line carrying capacity?
  25. 25. Which limit is usually decisive in long lines?
  26. 26 If the voltage is increased tenfold at the same power, how does the current change?
  27. 27 If the voltage increases tenfold at the same power, how does the transmission loss change?
  28. 28 Under what circumstances does the coronavirus become significant?
  29. 29 What is the purpose of transformers in changing voltage?
  30. 30 What risk does the breakage of the neutral conductor pose?
  31. 31 What does the negative-sequence component do in asynchronous motors?
  32. 32 What situation does over-compensation lead to?
  33. 33 What should be considered when selecting a capacitor in a harmonic environment?
  34. 34 In which system is the two-wattmeter method used?
  35. 35 Which quantities does the measuring instrument use to measure active power?
  36. 36 What data is dynamic line rating based on?
  37. 37 Where is the zero component observed?
  38. 38 Why is phase sequence verification important?
  39. 39 What is the simplest way to reduce load imbalance?
  40. 40 What is the unit of apparent power?